Conduit shall be Anaconda SEALTITE® Type CW. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 1/2" thru 1-1/4". Conduit shall have a sunlight resistant and flame retardant PVC jacket in electrical trade sizes 1/2" thru 3". Conduit shall be UL listed, CSA certified and IP 67 rated when installed with approved end connectors.

Unit of Measure

Specifications

Type

N/A CW

Electrical Trade Size

N/A 2 in53 mm

Length

N/A 100 ft30.48 m

Packaging

N/A Standard Reels

Inside Diameter

N/A 2.020 to 2.045 in51.308 to 51.943 mm

Outside Diameter

N/A 2.340 to 2.375 in59.436 to 60.325 mm

Approx. Inside Bend Radius

N/A 7.0 in177.8 mm

Approx. Weight per 100 ft

N/A 155 lbs70.3 kg

Color

N/A BLUE

Note

N/A

Other colors available upon request.
3/8" & 4" trade sizes available on special order.

Industry Certifications

N/A
UL Listed & CSA Certified

Cross-Reference #

N/A 261044 55-28-12-01 6407-30-00 CB CBLA-16 CBLT-2 ULBLUE

Core Material

N/A Galvanized Steel

Ingress Protection (IP) Rating

N/A Ingress Protection (IP) 66/67

Jacket Material

N/A Polyvinyl Chloride (PVC)

Jacket Benefits

N/A Liquid Tight Oil Resistant

Installation

N/A

  • Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations. Rated for temperature ranges -40ºF to + 176ºF (-40ºC to +80ºC).
  • Approved as an equipment grounding conductor in sizes 1/2" through 1-1/4, if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 1/2" and 60 amps or less for 3/4" through 1-1/4".
  • Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
  • Manufactured in a full range of trade sizes from 1/2" through 3".
  • Approved for direct burial and in concrete trade sizes 1/2" through 3".
  • Complies with UL Standard 360 File No. E18917; CSA C22.2 File No. 158897; and NEC Article 350.

NEC Articles

N/A

  • Article 250.118 (6) Equipment Grounding
  • Article 300.22 (D) Information Technology Equipment
  • Article 350 Liquid-Tight Flexible Metal Conduit (LFMC)
  • Article 501.10 (B) (2) Class I Div. 2
  • Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
  • Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
  • Article 620.21 Elevator Wiring Methods
  • Article 645.5 (E) (2) Under Raised Floors

Application

N/A

Computer Wiring Meets Requirements of NEC
Temperature Range: -40°F to +176°F (-40°C to +80°C)