Print Back
Thermoplastic PVC

Conduit shall be Anaconda SEALTITE® Type NMUA. Conduit shall be constructed of non-metallic PVC material and shall be used for inside, outside and corrosive applications in accordance with Article 356 of the National Electric Code. Conduit shall be used in applications requiring a temperature range of -17ºF to +176ºF (-27ºC to +80ºC) for dry locations. Conduit shall be UL listed and CSA certified as Type "B" non-metallic conduit. Conduit IP 67 rated when installed with approved end connectors.
Unit of Measure

Specifications

Type

N/A NMUA

Electrical Trade Size

N/A 3/4 in21 mm

Length

N/A 700 ft213.36 m

Packaging

N/A Standard Reels

Inside Diameter

N/A 0.820 to 0.840 in20.828 to 21.336 mm

Outside Diameter

N/A 1.030 to 1.050 in26.162 to 26.670 mm

Approx. Inside Bend Radius

N/A 4.5 in114.3 mm

Approx. Weight per 100 ft

N/A 16 lbs7.26 kg

Color

N/A GRAY

Industry Certifications

N/A
UL Listed & CSA Certified

Cross-Reference #

N/A 55-09-63-01 6003-46-00 81024 LFNC-B NM NM-12 NMUA NMUA-3/4

Core Material

N/A Polyvinyl Chloride (PVC)

Ingress Protection (IP) Rating

N/A Ingress Protection (IP) 65/66/67

Jacket Material

N/A Polyvinyl Chloride (PVC)

Jacket Benefits

N/A Liquid Tight Oil Resistant

Installation

N/A

  • Conduit used with standard connectors for non-metallic conduit Type B for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations. Rated for temperature ranges of -17ºF to +176ºF (-27ºC to +80ºC).
  • Complies with NEC Article 356 and UL Standard 1660 File No. E-211327; CSA C22.2 File No. 020817.
  • Easy to install and cuts easily.
  • Manufactured in a full range of trade sizes from 3/8" through 2".
  • Approved for direct burial and in concrete trade sizes 3/8" through 2".

NEC Articles

N/A

  • Article 250.102 Equipment Bonding Jumpers
  • Article 250.134 (B) Equipment Grounding
  • Article 300.22 (D) Information Technology Equipment
  • Article 356 Liquid-Tight Flexible Nonmetallic Conduit (LFNC-B)
  • Article 501.10 (B) (2) Class I Div. 2
  • Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
  • Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
  • Article 620.21 Elevator Wiring Methods
  • Article 645.5 (E) (2) Under Raised Floors

Application

N/A General Purpose Non-Metallic-Smooth Inner/Outer Wall
Temperature Range: of -17ºF to +176ºF (-27ºC to +80ºC).