Thermoplastic PVC jacket with integral bonding wire 3/8" through 1-1/4"

Conduit shall be Anaconda SEALTITE® Type HTUA. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 3/8" thru 1-1/4". Conduit shall have a sunlight resistant and flame retardant PVC jacket in electrical trade sizes 3/8" thru 4". Conduit shall be UL listed, CSA certified and IP 67 rated when installed with approved end connectors.
Unit of Measure

Specifications

Type

HTUA

Electrical Trade Size

1-1/4 in35 mm

Length

50 ft15.24 m

Packaging

Small Cartons

Inside Diameter

1.380 to 1.410 in35.052 to 35.814 mm

Outside Diameter

1.630 to 1.660 in41.402 to 42.164 mm

Approx. Inside Bend Radius

7.0 in177.8 mm

Approx. Weight per 100 ft

100 lbs45.36 kg

Color

GRAY

Optional Colors

Black

Industry Certifications


UL Listed & CSA Certified



Cross-Reference #

55-28-86-02 6905-24-00 80242 ATLA-14

Core Material

Galvanized Steel

Ingress Protection (IP) Rating

Ingress Protection (IP) 66/67

Jacket Material

Polyvinyl Chloride (PVC)

Jacket Benefits

Extreme Cold High Heat Liquid Tight Oil Resistant

Installation

N/A

  • Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations Rated for temperature ranges UL temps -51ºF to + 221ºF (-46ºC to +105ºC), CSA -51ºF to 167ºF (-46ºC to +75ºC).
  • Approved as an equipment grounding conductor in sizes 3/8" through 1-1/4" if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 3/8" and 1/2" and 60 amps or less for 3/4" through 1-1/4".
  • Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
  • Manufactured in a full range of trade sizes from 3/8" through 4".
  • Approved for direct burial and in concrete trade sizes 3/8" through 4".
  • Complies with UL Standard 360 File No. E18917; CSA C22.2 File No. 158897; and NEC Article 350.

NEC Articles

N/A

  • Article 250.118 (6) Equipment Grounding
  • Article 300.22 (D) Information Technology Equipment
  • Article 350 Liquid-Tight Flexible Metal Conduit (LFMC)
  • Article 501.10 (B) (2) Class I Div. 2
  • Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
  • Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
  • Article 620.21 Elevator Wiring Methods
  • Article 645.5 (E) (2) Under Raised Floors

Application

N/A Ideal for Use in Environments with Extreme Temperatures and UL Listing is Required
Temperature Range: -51ºF to +221ºF (-46ºC to +105ºC)