Conduit shall be Anaconda SEALTITE® Type ZHUA. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 3/8" thru 1-1/4". Conduit shall have a sunlight resistant, flame retardant, LOW SMOKE AND ZERO HALOGEN TPU jacket in electrical trade sizes 3/8" thru 4". Conduit shall be UL listed, and IP 67 rated when installed with approved end connectors.
Unit of Measure

Specifications

Type

N/A ZHUA

Electrical Trade Size

N/A 4 in103 mm

Length

N/A 25 ft7.62 m

Packaging

N/A Standard Carton

Inside Diameter

N/A 4.000 to 4.040 in101.600 to 102.616 mm

Outside Diameter

N/A 4.460 to 4.500 in113.284 to 114.300 mm

Inside Bend Radius

N/A 17 in431.8 mm

Approx. Weight per 100 ft

N/A 362 lbs164.2 kg

Color

N/A BLACK

Note

N/A Colors are available upon request.
Test data results obtained from an independent test laboratory. Consult factory for additional details.

Industry Certifications

N/A
UL Listed & CSA Certified

Cross-Reference #

N/A 6711-22-00 88192 LSZH ZHLA-19

Core Material

N/A Galvanized Steel

Ingress Protection (IP) Rating

N/A Ingress Protection (IP) 66/67

Jacket Material

N/A Thermoplastic Polyurethane (TPU)

Jacket Benefits

N/A Liquid Tight Oil Resistant Zero Halogen

Installation

N/A

  • Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations. Rated for temperature ranges -40ºF to + 176ºF (-40ºC to +80ºC).
  • Approved as an equipment grounding conductor in sizes 3/8" through 1-1/4" if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 3/8" and 1/2" and 60 amps or less for 3/4" through 1-1/4".
  • Suitable for use in hazardous locations per NEC Article 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
  • Manufactured in a full range of sizes from 3/8" through 4".
  • Approved for direct burial and in concrete trade sizes 3/8" through 4".
  • Complies with UL Standard 360 File No. E18917; and NEC Article 350.

NEC Articles

N/A

  • Article 250.118 (6) Equipment Grounding
  • Article 300.22 (D) Information Technology Equipment
  • Article 350 Liquid-Tight Flexible Metal Conduit (LFMC)
  • Article 501.10 (B) (2) Class I Div. 2
  • Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
  • Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
  • Article 620.21 Elevator Wiring Methods
  • Article 645.5 (E) (2) Under Raised Floors

Application

N/A For Restricted or Self-Contained Ventilation Areas
Temperature ranges -40°F to + 176°F (-40°C to +80°C)

MEETS or EXCEEDS the following Standards

N/A

  • Flame Spread Index ASTM E162
  • Smoke Density (Generation) ASTM E662
  • Toxic Gas Generation Bombardier SMP-800C
  • Jacket Material is U.L. 94 Certified
  • Conduit is U.L. 360 Listed