Thermoplastic PVC

Conduit shall be Anaconda SEALTITE® Type NMUA. Conduit shall be constructed of non-metallic PVC material and shall be used for inside, outside and corrosive applications in accordance with Article 356 of the National Electric Code. Conduit shall be used in applications requiring a temperature range of -17ºF to +176ºF (-27ºC to +80ºC) for dry locations. Conduit shall be UL listed and CSA certified as Type "B" non-metallic conduit. Conduit IP 67 rated when installed with approved end connectors.
Unit of Measure

Specifications

Type

NMUA

Electrical Trade Size

3/4 in21 mm

Length

100 ft30.48 m

Packaging

Standard Carton

Inside Diameter

0.820 to 0.840 in20.828 to 21.336 mm

Outside Diameter

1.030 to 1.050 in26.162 to 26.670 mm

Approx. Inside Bend Radius

4.5 in114.3 mm

Approx. Weight per 100 ft

16 lbs7.26 kg

Color

GRAY

Industry Certifications


UL Listed & CSA Certified

Cross-Reference #

58-04-63-01 6003-30-00 81022 LFNC-B NM NM-12 NMUA NMUA-3/4

Core Material

Polyvinyl Chloride (PVC)

Ingress Protection (IP) Rating

Ingress Protection (IP) 65/66/67

Jacket Material

Polyvinyl Chloride (PVC)

Jacket Benefits

Liquid Tight Oil Resistant

Installation

N/A

  • Conduit used with standard connectors for non-metallic conduit Type B for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations. Rated for temperature ranges of -17ºF to +176ºF (-27ºC to +80ºC).
  • Complies with NEC Article 356 and UL Standard 1660 File No. E-211327; CSA C22.2 File No. 020817.
  • Easy to install and cuts easily.
  • Manufactured in a full range of trade sizes from 3/8" through 2".
  • Approved for direct burial and in concrete trade sizes 3/8" through 2".

NEC Articles

N/A

  • Article 250.102 Equipment Bonding Jumpers
  • Article 250.134 (B) Equipment Grounding
  • Article 300.22 (D) Information Technology Equipment
  • Article 356 Liquid-Tight Flexible Nonmetallic Conduit (LFNC-B)
  • Article 501.10 (B) (2) Class I Div. 2
  • Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
  • Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
  • Article 620.21 Elevator Wiring Methods
  • Article 645.5 (E) (2) Under Raised Floors

Application

N/A General Purpose Non-Metallic-Smooth Inner/Outer Wall
Temperature Range: of -17ºF to +176ºF (-27ºC to +80ºC).