Construction
- Constructed of continuously interlocked hot dipped zinc galvanized steel core for exceptional crush and corrosion resistance.
- Approved for direct burial and in concrete trade sizes 3/8" through 3".
- Durable, sunlight resistant and flame retardant thermoplastic PVC jacket that resists heat, oil and chemical breakdown.
Compliant with NEC Articles
- 300.22 (D) Information Technology Equipment
- 250.102, 250.118(5) and 250.134(B) Equipment Grounding
- Suitable for Hazardous Locations per NEC Articles
- 501.10(B)(2) Class I Div. 2
- 502.10(A)(2) Class II Div. 1 & 2
- 503.10(A)(3) and (B) Class III Div. 1 & 2
- 350 Liquid-tight Flexible Metal Conduit (LFMC)
- 645.5 (E) (2) Under raised floors
- CSA Certified “Heavy-Duty” 1/2” and up
Applications
- Protect wiring and cable in data centers and networks
- Approved for direct burial and in concrete trade sizes 1/2”-3”
- Protection of 1000 volt and lower potential circuits
- Approved as an equipment grounding conductor in sizes 3/8” through 1-1/4” if the total grounding path is 6 feet or less and the circuit conductors are protected by over-current devices rated at 20 amps or less for 3/8” and 1/2” and 60 amps or less for 3/4” through 1-1/4”
- Approved for installation under raised floors
Certifications
UL 360 DXHR.E18917 / CSA Approved C22.2 #LL15275 / RoHS WEEE COMPLIANT / CSA Certified “Heavy-Duty” 1/2” and up
Meets requirements of NFPA 79 (2024 Edition) Section 13.5.4 LFMC and NFPA 130 (2023 Edition) Section 8.6.7.4 LFMC
Recommended ANACONDA SEALTITE® Fittings
Compact 316 Stainless Steel for the best corrosion resistance
Compact Nickel-Plated Brass for next level corrosion resistance
Items |
/Asset/a1019.jpg 34512 Type CW - Computer Blue Liquid-Tight Flexible Metal Conduit (LFMC) |
/Asset/a1019.jpg 34522 Type CW - Computer Blue Liquid-Tight Flexible Metal Conduit (LFMC) |
/Asset/a1019.jpg 34531 Type CW - Computer Blue Liquid-Tight Flexible Metal Conduit (LFMC) |
/Asset/a1019.jpg 34541 Type CW - Computer Blue Liquid-Tight Flexible Metal Conduit (LFMC) |
/Asset/a1019.jpg 34551 Type CW - Computer Blue Liquid-Tight Flexible Metal Conduit (LFMC) |
|||||
Description |
N/A
Thermoplastic PVC jacket with integral bonding wire 1/2" through 1-1/4" |
N/A
Thermoplastic PVC jacket with integral bonding wire 1/2" through 1-1/4" |
N/A
Thermoplastic PVC jacket with integral bonding wire 1/2" through 1-1/4" |
N/A
Thermoplastic PVC jacket with integral bonding wire 1/2" through 1-1/4" |
N/A
Conduit shall be Anaconda SEALTITE® Type CW. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 1/2" thru 1-1/4". Conduit shall have a sunlight resistant and flame retardant PVC jacket in electrical trade sizes 1/2" thru 3". Conduit shall be UL listed, CSA certified and IP 67 rated when installed with approved end connectors. |
|||||
Type | N/A CW | |||||||||
Electrical Trade Size | N/A 1/2 in16 mm | N/A 3/4 in21 mm | N/A 1 in27 mm | N/A 1-1/4 in35 mm | N/A 1-1/2 in41 mm | |||||
Length | N/A 100 ft30.48 m | N/A 100 ft30.48 m | N/A 100 ft30.48 m | N/A 50 ft15.24 m | N/A 50 ft15.24 m | |||||
Packaging | N/A Standard Carton | |||||||||
Inside Diameter | N/A 0.622 to 0.642 in15.799 to 16.307 mm | N/A 0.820 to 0.840 in20.828 to 21.336 mm | N/A 1.041 to 1.066 in26.441 to 27.076 mm | N/A 1.380 to 1.410 in35.052 to 35.814 mm | N/A 1.575 to 1.600 in40.005 to 40.640 mm | |||||
Outside Diameter | N/A 0.822 to 0.840 in20.879 to 21.336 mm | N/A 1.030 to 1.050 in26.162 to 26.670 mm | N/A 1.290 to 1.315 in32.766 to 33.401 mm | N/A 1.630 to 1.660 in41.402 to 42.164 mm | N/A 1.865 to 1.900 in47.371 to 48.260 mm | |||||
Approx. Inside Bend Radius | N/A 3.5 in88.9 mm | N/A 5.0 in127 mm | N/A 6.3 in160 mm | N/A 7.0 in177.8 mm | N/A 5.5 in139.7 mm | |||||
Approx. Weight per 100 ft | N/A 30 lbs13.6 kg | N/A 43 lbs19.5 kg | N/A 71 lbs32.2 kg | N/A 94 lbs42.6 kg | N/A 112 lbs50.8 kg | |||||
Installation |
N/A
|
|||||||||
Color | N/A BLUE | |||||||||
Optional Colors | N/A | |||||||||
NEC Articles |
N/A
|
|||||||||
Note |
N/A
Other colors available upon request. |
|||||||||
Application |
N/A
Computer Wiring Meets Requirements of NEC |
|||||||||
Industry Certifications |
N/A
UL Listed & CSA Certified |
|||||||||
Core Material | N/A Galvanized Steel | |||||||||
Ingress Protection (IP) Rating | N/A Ingress Protection (IP) 66/67 | |||||||||
Jacket Material | N/A Polyvinyl Chloride (PVC) | |||||||||
Jacket Benefits | N/A Liquid Tight Oil Resistant | |||||||||
|