Type CNP - Non-conductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC)
Sealtite® Non-Metallic Conduit
Construction
- Smooth inner wall PVC core covered with a nylon fiber braid bonded to a smooth, oil resistant, PVC cover.
- Durable, sunlight resistant and flame retardant thermoplastic PVC that resists heat, oil and chemical breakdown.
- Color: Orange or gray
- Temperature range: -4°F to +140°F (-20°C to +60°C)
Compliant with NEC Articles
- 300.22 (D) Information Technology Equipment
- Suitable for Hazardous Locations per NEC Articles
- 501.10(B)(2) Class I Div. 2
- 502.10(A)(2) Class II Div. 1 & 2
- 503.10(A)(3) and (B) Class III Div. 1 & 2
- 356 Liquid tight Flexible Nonmetal Conduit (LFNC-A)
- 645.5 (E) (2) Under raised floors
Certifications
UL 1660 DXOQ.E75863 / NEC Article 356 / CSA #LL15275-10 / RoHS WEEE COMPLIANT
Meets requirements of NFPA 79 (2024 Edition) Section 13.5.4 LFNC
Recommended ANACONDA SEALTITE® fittings
Unit of Measure
Items |
/Asset/a1039.jpg 38602 Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC) |
/Asset/a1039.jpg 38612 Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC) |
/Asset/a1039.jpg 38622 Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC) |
/Asset/a1039.jpg 38601 Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC) |
/Asset/a1039.jpg 38611 Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC) |
|||||
Description |
N/A
Thermoplastic PVC Conduit shall be Anaconda SEALTITE® Type CNP. Conduit shall be constructed of smooth inner thermoplastic PVC core with outer oil-resistant and sunlight resistant PVC outer cover. Conduit shall have nylon reinforcing layer between the core and outer cover. Conduit shall be assembled with approved fittings to provide liquid-tight raceway for wiring. Conduit shall be UL listed and CSA certified as a Type "A" non-metallic conduit and be used in applications requiring a temperature range of -4ºF to +140ºF (-20ºC to +60ºC). Conduit IP 67 rated when installed with approved end connectors. |
|||||||||
Type | N/A CNP | |||||||||
Electrical Trade Size | N/A 3/8 in12 mm | N/A 1/2 in16 mm | N/A 3/4 in21 mm | N/A 3/8 in12 mm | N/A 1/2 in16 mm | |||||
Length | N/A 100 ft30.48 m | N/A 100 ft30.48 m | N/A 100 ft30.48 m | N/A 250 ft76.2 m | N/A 200 ft60.96 m | |||||
Packaging | N/A Small Cartons | N/A Small Cartons | N/A Small Cartons | N/A Standard Carton | N/A Standard Carton | |||||
Inside Diameter | N/A 0.485 to 0.505 in12.319 to 12.827 mm | N/A 0.620 to 0.640 in15.748 to 16.256 mm | N/A 0.815 to 0.835 in20.701 to 21.209 mm | N/A 0.485 to 0.505 in12.319 to 12.827 mm | N/A 0.620 to 0.640 in15.748 to 16.256 mm | |||||
Outside Diameter | N/A 0.755 to 0.775 in19.177 to 19.685 mm | N/A 0.910 to 0.930 in23.114 to 23.622 mm | N/A 1.150 to 1.170 in29.210 to 29.718 mm | N/A 0.755 to 0.775 in19.177 to 19.685 mm | N/A 0.910 to 0.930 in23.114 to 23.622 mm | |||||
Approx. Inside Bend Radius | N/A 2.5 in63.5 mm | N/A 3.0 in76.2 mm | N/A 4.0 in101.6 mm | N/A 2.5 in63.5 mm | N/A 3.0 in76.2 mm | |||||
Approx. Weight per 100 ft | N/A 15 lbs6.8 kg | N/A 21 lbs9.53 kg | N/A 30 lbs13.61 kg | N/A 15 lbs6.8 kg | N/A 21 lbs9.53 kg | |||||
Installation |
N/A
|
|||||||||
Color | N/A Orange | |||||||||
Optional Colors | N/A Gray | |||||||||
NEC Articles |
N/A
|
|||||||||
Note | N/A Colors available on request. | |||||||||
Application |
N/A
Where Abrasion or Physical Abuse are Factors, Constant Flexing or Movement Temperature Range: -4ºF to +140ºF (-20ºC to +60ºC) |
|||||||||
Industry Certifications |
N/A
UL Listed & CSA Certified |
|||||||||
Core Material | N/A Polyvinyl Chloride (PVC) | |||||||||
Ingress Protection (IP) Rating | N/A Ingress Protection (IP) 66/67 | |||||||||
Jacket Material | N/A Polyvinyl Chloride (PVC) | |||||||||