Construction

  • Smooth inner wall PVC core covered with a nylon fiber braid bonded to a smooth, oil resistant, PVC cover. 
  • Durable, sunlight resistant and flame retardant thermoplastic PVC that resists heat, oil and chemical breakdown.
  • Color: Orange or gray
  • Temperature range: -4°F to +140°F (-20°C to +60°C)

Compliant with NEC Articles

  • 300.22 (D) Information Technology Equipment
  • Suitable for Hazardous Locations per NEC Articles
    • 501.10(B)(2) Class I Div. 2
    • 502.10(A)(2) Class II Div. 1 & 2
    • 503.10(A)(3) and (B) Class III Div. 1 & 2
  • 356 Liquid tight Flexible Nonmetal Conduit (LFNC-A)
  • 645.5 (E) (2) Under raised floors

Certifications

UL 1660 DXOQ.E75863 / NEC Article 356 / CSA #LL15275-10 / RoHS WEEE COMPLIANT
Meets requirements of NFPA 79 (2024 Edition) Section 13.5.4 LFNC

Recommended ANACONDA SEALTITE® fittings

Type A Nickel-Plated Brass

Unit of Measure
Items
Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC)

Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC)

Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC)

Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC)

Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC)

Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC)

Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC)

Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC)

Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC)

Type CNP - Nonconductive Conduit Liquid-Tight Flexible Non-Metallic Conduit (LFNC)
Description N/A Thermoplastic PVC

Conduit shall be Anaconda SEALTITE® Type CNP. Conduit shall be constructed of smooth inner thermoplastic PVC core with outer oil-resistant and sunlight resistant PVC outer cover. Conduit shall have nylon reinforcing layer between the core and outer cover. Conduit shall be assembled with approved fittings to provide liquid-tight raceway for wiring. Conduit shall be UL listed and CSA certified as a Type "A" non-metallic conduit and be used in applications requiring a temperature range of -4ºF to +140ºF (-20ºC to +60ºC). Conduit IP 67 rated when installed with approved end connectors.
Type N/A CNP
Electrical Trade Size N/A 3/8 in12 mm N/A 1/2 in16 mm N/A 3/4 in21 mm N/A 3/8 in12 mm N/A 1/2 in16 mm
Length N/A 100 ft30.48 m N/A 100 ft30.48 m N/A 100 ft30.48 m N/A 250 ft76.2 m N/A 200 ft60.96 m
Packaging N/A Small Cartons N/A Small Cartons N/A Small Cartons N/A Standard Carton N/A Standard Carton
Inside Diameter N/A 0.485 to 0.505 in12.319 to 12.827 mm N/A 0.620 to 0.640 in15.748 to 16.256 mm N/A 0.815 to 0.835 in20.701 to 21.209 mm N/A 0.485 to 0.505 in12.319 to 12.827 mm N/A 0.620 to 0.640 in15.748 to 16.256 mm
Outside Diameter N/A 0.755 to 0.775 in19.177 to 19.685 mm N/A 0.910 to 0.930 in23.114 to 23.622 mm N/A 1.150 to 1.170 in29.210 to 29.718 mm N/A 0.755 to 0.775 in19.177 to 19.685 mm N/A 0.910 to 0.930 in23.114 to 23.622 mm
Approx. Inside Bend Radius N/A 2.5 in63.5 mm N/A 3.0 in76.2 mm N/A 4.0 in101.6 mm N/A 2.5 in63.5 mm N/A 3.0 in76.2 mm
Approx. Weight per 100 ft N/A 15 lbs6.8 kg N/A 21 lbs9.53 kg N/A 30 lbs13.61 kg N/A 15 lbs6.8 kg N/A 21 lbs9.53 kg
Installation N/A
  • Conduit used with standard connectors for non-metallic conduit Type A for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations. Rated for temperature ranges of -4ºF to +140ºF (-20ºCto +60ºC).
  • Complies with UL Standard 1660 Type A conduit File No. E-75863; CSA C22.2 File No. LL15257; and NEC Article 356.
  • Easy to install and cuts easily.
  • Manufactured in a full range of trade sizes from 3/8" through 2".
  • Flexible, but tough; crush, abrasion and strain resistant. Where abrasion, physical abuse or constant flexing are a factor.
Color N/A Orange
Optional Colors N/A Gray
NEC Articles N/A
  • Article 250.102 Equipment Bonding Jumpers
  • Article 250.134 (B) Equipment Grounding
  • Article 300.22 (D) Information Technology Equipment
  • Article 356 Liquid-Tight Flexible Nonmetallic Conduit (LFNC-A)
  • Article 501.10 (B) (2) Class I Div. 2
  • Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
  • Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
  • Article 620.21 Elevator Wiring Methods
  • Article 645.5 (E) (2) Under Raised Floors
Note N/A Colors available on request.
Application N/A Where Abrasion or Physical Abuse are Factors, Constant Flexing or Movement
Temperature Range: -4ºF to +140ºF (-20ºC to +60ºC)
Industry Certifications N/A UL Listed & CSA Certified
Core Material N/A Polyvinyl Chloride (PVC)
Ingress Protection (IP) Rating N/A Ingress Protection (IP) 66/67
Jacket Material N/A Polyvinyl Chloride (PVC)
Jacket Benefits N/A Liquid Tight Oil Resistant