• Type A fittings .jpg

    Construction

    • Nickel-plated brass fitting with six-piece construction, consisting of a gland nut, TPE clamping ring, ferrule, body, seal inset into the body and insulated throat.

    Description

    • IP 66/67 rated when installed with approved conduit and tightened to UL-514B/CSA C22.2 18.3 torque specifications
    • The fittings have superior pullout strength on Type CNP LFNC-A conduit, surpassing plastic fittings
    • Halogen Free fittings
    • Temperature range: -49ºF to +221ºF (-45ºC to +105ºC)
    • The 90-degree fitting has a sweeping bore for easier wire pulling
    • SEALTITE® Nickel-plated Brass Type A fittings installed on Type CNP conduit pass UL 514B pull tests

    Applications

    • Approved for both exposed and concealed locations
    • Fitting for Non-metallic flexible conduit (LFNC-A)
    • Meet NEMA FB-1 standard and UL 514B standard
    • Suitable for Hazardous Locations per NEC Articles
      • 501.10 (B) (2) Class I Div. 2
      • 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
      • 503.10 (A) (3) and (B) Class III Div. 1 & 2

    Certifications

    cULus 514B Approved DWTT.E234207 / RoHS WEEE COMPLIANT

  • Food Grade - Straight

    These compact, stainless steel AISI-316 Food Grade fittings can be used with all ANACONDA SEALTITE® conduit, except for Type CNP, NMUA and NMEF.

    The fitting design has round corners and a smooth profile to minimize risk of bacteria deposits and to promote cleaning. The fittings have excellent resistance to corrosion.

    • Compliant with National Sanitation Foundation (NSF) requirements for liquid tight flexible conduit fittings for Food Zone Non-Contact and Splash Zone.
    • Evaluated and in compliance with the current criteria for Hygienic Equipment Design of the EHEDG (report DTU CHD DR 2017 8037-088-3) locations.
    • Special approvals per FDA guideline CFR21: Halogen free, TPE seals are formulated for food and beverage applications.
    • Fittings have six parts (counter nut, upper seal, clamping ring, ferrule, body and 304SS locknut) providing for an IP 68 connection on approved conduit.
    • Stainless steel AISI-316 fitting, consisting of six parts (counter nut, upper seal, clamping ring, ferrule, body and 304SS locknut)
    • Hygienically designed with rounded corners and a smooth contourless profile to minimize the risk of bacteria deposits and to promote easy cleaning
    • Evaluated and in compliance with the current criteria for Hygienic Equipment Design of the EHEDG (report .DTU CHD DR 2017 8037-088-3) locations

    Specifications

    • AISI-316 body with AISI-304 ferrule and counter nut, TPE clamping ring and locknut
    • Color: Metallic
    • Temperature range: -40º F to +221º F (-40º C to +105º C)

    Applications

    • Rated for Food Zone Non-Contact and Splash Zone applications
    • For metallic flexible conduit
    • Premium Stainless 316 for the best corrosion resistance
    • Compact design for tight spaces
    • Suitable for hazardous locations per NEC Articles
      • 501.10 (B) (2) Class I Div. 2
      • 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
      • 503.10 (A) (3) and (B) Class III Div. 1 & 2

    Certifications

    cULus 514B Approved DWTT.E234207 / IP 68 rated according EN 60529, IP 69 rated according DIN 40050-9 (till 40 Bar high pressure) / NSF/ANSI 169

  • 316 Stainless steel fitting strt

    Construction

    • 316 Stainless Steel fitting, has a four piece construction consisting of a gland nut, PA6 clamping ring, high tensile ferrule and body.
    • Compact design is ideal for tight spaces: 20% smaller and 35% lighter than standard SEALTITE® fittings
    • Superior Stainless Steel 316 corrosion resistance, strength and durability
    • Halogen Free fittings
    • IP 66/67 rated when installed with approved conduit and tightened to UL-514B/CSA C22.2 18.3 torque specifications
    • Temperature range: -49ºF to +221ºF (-45ºC to +105ºC)

    Applications

    • Approved for both exposed and concealed locations
    • Fitting for metallic flexible conduit
    • Meet NEMA FB-1 standard and UL 514B standard
    • Suitable for Hazardous Locations per NEC Articles
      • 501.10 (B) (2) Class I Div. 2
      • 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
      • 503.10 (A) (3) and (B) Class III Div. 1 & 2

    Certifications

    cULus 514B Approved DWTT.E234207 / RoHS WEEE COMPLIANT

     

     

  • 316 Stainless steel fitting strt

    Construction

    • Nickel plated brass fitting, has a four piece construction consisting of a gland nut, PA6 clamping ring, ferrule and body.
    • Compact design is ideal for tight spaces: 20% smaller and 35% lighter than standard SEALTITE® fittings
    • IP 66/67 rated when installed with approved conduit and tightened to UL-514B/CSA C22.2 18.3 torque specifications
    • Temperature range: -49ºF to +221ºF (-45ºC to +105ºC)

    Applications

    • Approved for both exposed and concealed locations
    • Fitting for metallic flexible conduit
    • Halogen Free fittings
    • Meet NEMA FB-1 standard and UL 514B standard
    • Suitable for Hazardous Locations per NEC Articles
      • 501.10 (B) (2) Class I Div. 2
      • 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
      • 503.10 (A) (3) and (B) Class III Div. 1 & 2

    Certifications

    cULus 514B Approved DWTT.E234207 / RoHS WEEE COMPLIANT

     

     

  • ISO STRT COMPCT

    Construction

    • Nickel plated brass fitting, has a four piece construction consisting of a gland nut, PA6 clamping ring, ferrule and body.
    • Compact design is ideal for tight spaces: 20% smaller and 35% lighter than standard SEALTITE® fittings
    • IP 66/67 rated when installed with approved conduit and tightened to UL-514B/CSA C22.2 18.3 torque specifications
    • Temperature range: -49ºF to +221ºF (-45ºC to +105ºC)

    Applications

    • Approved for both exposed and concealed locations
    • Fitting for metallic flexible conduit
    • Meet NEMA FB-1 standard and UL 514B standard
    • Suitable for Hazardous Locations per NEC Articles
      • 501.10 (B) (2) Class I Div. 2
      • 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
      • 503.10 (A) (3) and (B) Class III Div. 1 & 2

    Certifications

    cULus 514B Approved DWTT.E234207 / RoHS WEEE COMPLIANT

  • Steel Straight fitting

    Construction

    • Zinc-plated steel fitting, has a five piece construction consisting of a gland nut, sealing ring, high tensile grounding ferrule, insulated throat and body.
    • IP 66/67 rated when installed with approved conduit and tightened to UL-514B/CSA C22.2 18.3 torque specifications
    • Corrosion resistant, protecting from moisture and oil
    • Temperature range: -49ºF to +221ºF (-45ºC to +105ºC)

    Applications

    • Approved for both exposed and concealed locations
    • Fitting for metallic flexible conduit
    • Meet NEMA FB-1 standard and UL 514B standard
    • Suitable for Hazardous Locations per NEC Articles
      • 501.10 (B) (2) Class I Div. 2
      • 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
      • 503.10 (A) (3) and (B) Class III Div. 1 & 2

    Certifications

    UL 514B TEOZ.E472179 / RoHS WEEE COMPLIANT

  • TYPE A FITTING STRT

    Construction

    • Zinc-plated steel fitting, has a 3 piece construction consisting of a two-piece gland nut, ferrule (PA6), and body
    • Included sealing ring and galvanized steel lock nut
    • Throat of the fitting has a plastic insulator

    Installation

    • Fitting is ideal for use with standard liquid tight non-metallic Type A conduit
    • IP 67 Rated when installed with approved conduit
    • Approved for both exposed and concealed locations
    • Temperature range: -49ºF to + 221ºF (-45ºC to +105ºC)
    • Suitable for use in hazardous locations per NEC Articles
      • Article 501.10 (B) (2) Class I Div. 2
      • Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
      • Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
      • Article 620.21 Elevator Wiring Methods
      • Article 645.5 (E) (2) Under Raised Floors

    Certifications

    UL LISTED #E322120 / CSA Approved #620817 / RoHS WEEE COMPLIANT

  • NMUA-STRAIGHT2

    Construction

    • All type Nylon 66 construction with an o-ring and steel lock nut included

    Description

    • Reusable and durable fittings are flame retardant and resist salt water, weak acids, gasoline, alcohol, oil grease and common solvents

    Specifications

    • Color: Gray
    • Temperature range: Dry: (0°F to +194°F (-18°C to +90°C)
    • UV (sunlight) resistant

    Applications

    • Fittings used with standard non-metallic Type B conduit for easy installation
    • Approved for both exposed and concealed locations
    • Easy to install, by pushing the non-metallic conduit onto the smooth ferrule and tightening the sealing nut
    • Manufactured in a full range of trade sizes from 3/8” through 2”
    • Complies with NEC Article 356 and UL Standard 514B File No. E-322120
    • Meet NEMA FB-1 standard
    • Straight fittings approved for direct burial and in concrete trade sizes 3/8” through 2”
    • With approved conduit. fittings are rated IP 66/67

    Compliant with NEC ARTICLES

    • Article 250.102 Equipment Bonding Jumpers
    • Article 250.134 (B) Equipment Grounding
    • Article 356 Liquid tight Flexible Nonmetallic Conduit (LFNC-B)
    • Suitable for hazardous locations per NEC Articles
      • Article 501.10 (B) (2) Class I Div. 2
      • Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
      • Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
      • Article 620.21 Elevator Wiring Methods
      • Article 645.5 (E) (2) Under Raised Floors

    Certifications

    UL LISTED #E322120 / CSA Approved #620817 / RoHS WEEE COMPLIANT

  • ATEX 316

    NOTE: SEALTITE® ATEX fittings are available for European or international applications. This product is not UL listed. This product is not approved for use in NEC Hazardous Locations. 
    Care must be taken when applying these to North American installations. The user is responsible for safe use and compliance with local regulations.   

    Construction

    • Stainless Steel Type 316 fitting, has a five piece construction consisting of a gland nut, sealing ring, high tensile grounding cone, barrier container and body
    • A two-part compound epoxy seal is supplied to create the barrier
    • Excellent corrosion resistance, strength and durability

    Description

    • Explosion Proof fittings for any SEALTITE® conduit (except CNP)
    • IECEx-ATEX approved barrier fittings to provide seal around loose wires inside a SEALTITE® conduit
    • A barrier around loose wires is created with a bi-compound epoxy seal supplied with each fitting
    • IP 67 on the conduit and IP 66 between fitting and switchbox
    • Excellent corrosion resistance with AISI-316 Stainless Steel

    NOTE: For IECEx-ATEX applications, the fitting must be installed in pre-cut threads, without a locknut.

    Specifications

    • AISI-316 Stainless Steel with PTFE clamping ring
    • Separate two-compound epoxy is provided for creating a barrier
    • Color: Metallic
    • Temperature range: -76°F to +266°F (-60°C to +130°C)

    Applications

    • Metallic flexible conduit
    • Explosion-proof areas where Zone system used
    • Machinery for export to other countries where Zone system used
    • Superior corrosion resistance with 316 Stainless Steel

    Certifications

    IECEx-ATEX certified: CE0080 I M2 / II 2 GD / Ex d II C / Ex e II/ Ex d I / Ex tD A 21 IP 66 

  • SS straight fittings

    Construction

    • Stainless steel (AISI-304) fitting, consisting of 4 parts (locknut, clamping ring, ferrule and body.)
    • The counter nut and body are stainless steel (AISI-304). The ferrule is nickel plated brass. The clamping ring and insert are PA6.
    • Included sealing washer and locknut provides a means for connecting the fitting to junction boxes
    • IP 66/67 rated when installed with approved conduit and tightened to UL-514B/CSA C22.2 18.3 torque specifications
    • Temperature range: -49ºF to +221ºF (-45ºC to +105ºC)
    • Premium Stainless 304 for corrosion resistance

    Applications 

    • Fittings for metallic flexible conduit
    • Compact design for tight spaces
    • Halogen Free
    • Approved for both exposed and concealed locations
    • Meet NEMA FB-1 standard and UL 514B standard
    • Suitable for hazardous locations per NEC Articles
      • 501.10 (B) (2) Class I Div. 2
      • 502.10 (A) (2) and (B) (2) Class II Div.1 & 2
      • 503.10 (A) (3) and (B) Class III Div. 1 & 2

    Certifications
    cULus 514B Approved DWTT.E234207 / RoHS WEEE COMPLIANT